Safety information & warnings:
Risk of electric shock: Installation, connection and commissioning may only be carried out by a qualified electrician in accordance with the applicable installation regulations. Before working, disconnect the supply, secure it against reconnection and verify that it is de-energised.
Risk of fire: Rated current, tripping characteristic, breaking capacity and type must match the installation and the cable cross-section. Incorrectly selected devices may cause fire or personal injury.
Test residual current devices with the test button after installation and regularly thereafter.
Observe the manufacturer's operating and installation instructions. Use only as intended.
Angaben laut EU-Produktsicherheitsverordnung (GPSR):
Hersteller:![]()
Hager Vertriebsgesellschaft mbH & Co. KG
Zum Gunterstal
66440 Blieskastel
Tel: +49 6842 945 0
E-Mail: info@hager.de

Hager CDS463D fault current switch 4 polig 6kA 63A 30mA Type A QuickConnect
4 polig 6kA 63A 30mA Type A QuickConnect fault current protection switch according to EN 61008-1, DIN EN 61008-2-1 and VDE 0664 Part 10 + 11. QuickConnect terminal according to DIN EN 60898-1, VDE 0641-11 at access up to 63 A, IP2x touch protection according to DIN VDE 0106 part 100, blue test button and fault current display. Simple individual removal from the phase rail composite. With VDE characters. Suitable for subsequent installation of additional equipment. Labeling option directly on the device. Suitable for subsequent installation of additional equipment. Nominal current: 63 A Type of differential protection: A Sensitivity: 30 mA Number of poles: 4 P Impact current strength (impulsive fault currents 8/20μs): 0.25 kA Number of modules: 4 Frequency: 50 Hz
| Rated current | 63 A |
| Type of differential protection | A |
| Sensitivity | 30 mA |
| Number | 4 P |
| Impact current resistance (pulse fault currents 8/20μs) | 0,25 |
| Number of modules | 4 |
| Frequency | 50 Hz |
| Assembly type | DIN rail |
| Connection type | Screw technology |
| Connection cross section with flexible conductor | 16mm2 |
| Connection cross section for rigid conductor | 25mm2 |
| Torque | 2.8 Nm |
| Type of protection | IP20 |
| Insulation voltage | 500 V |
| Impact strength | 4 kV |
| Additional equipment possible | 1 |
| Operating temperature | -25 to 40 °C |
| Machine life mechanical switching games | 4000 |
| Device life, electrical switching games | 2000 |
| Total loss power at rated current | 18.5 W |
| Degree of contamination according to IEC 60664 / IEC 60947-2 | 2 |
| Height above N.N. | 2000 m |
| Rated current at 30° C | 63 A |
| Storage temperature | -55 to 70 °C |
| Height installed product | 83 mm |
| Wide installed product | 70 mm |
| Deep Installed Product | 70 mm |
Angaben laut EU-Produktsicherheitsverordnung (GPSR):
Hersteller:![]()
Hager Vertriebsgesellschaft mbH & Co. KG
Zum Gunterstal
66440 Blieskastel
Tel: +49 6842 945 0
E-Mail: info@hager.de