FI

Hager CDS240D Fehlerstromschutzschalter 2 polig 6kA 40A 30mA Typ A QuickConnect
Hager CDS240D fault current switch 2 polig 6kA 40A 30mA Type A QuickConnect
3-7 working days
2 polig 6kA 40A 30mA Type A QuickConnect fault current protection switch according to EN 61008-1, DIN EN 61008-2-1 and VDE 0664 Part 10 + 11. QuickConnect terminal according to DIN EN 60898-1, VDE 0641-11 at access up to 63 A, IP2x touch protection according to DIN VDE 0106 part 100, blue test button and fault current display. Simple individual removal from the phase rail composite. With VDE characters. Suitable for subsequent installation of additional equipment. Labeling option directly on the device. Suitable for subsequent installation of additional equipment. Nominal current: 40 A Type of differential protection: A Sensitivity: 30 mA Number of poles: 2 P Impact current strength (impulsive fault currents 8/20μs): 0.25 kA Number of modules: 2 Frequency: 50 HzRated current40 AType of differential protectionASensitivity30 mANumber2 PImpact current resistance (pulse fault currents 8/20μs)0,25Number of modules2Frequency50 HzAssembly typeDIN railConnection typeQuickConnectConnection cross section with flexible conductor16mm2Connection cross section for rigid conductor25mm2Torque2.8 NmType of protectionIP20Insulation voltage500 VImpact strength4 kVAdditional equipment possible1Operating temperature-25 to 40 °CMachine life mechanical switching games4000Device life, electrical switching games2000Total loss power at rated current9.2 WDegree of contamination according to IEC 60664 / IEC 60947-22Height above N.N.2000 mRated current at 30° C40 AStorage temperature-55 to 70 °CHeight installed product83 mmWide installed product35 mmDeep Installed Product70 mm
€76.05
Hager CDS225D Fehlerstromschutzschalter 2 polig 6kA 25A 30mA Typ A QuickConnect
Hager CDS225D fault current switch 2 polig 6kA 25A 30mA Type A QuickConnect
3-7 working days
2 polig 6kA 25A 30mA Type A QuickConnect. EN 61008-1, DIN EN 61008-2-1 and VDE 0664 Part 10 + 11. QuickConnect terminal according to DIN EN 60898-1, VDE 0641-11 at access up to 63 A, IP2x touch protection according to DIN VDE 0106 part 100, blue test button and fault current display. Simple individual removal from the phase rail composite. With VDE characters. Suitable for subsequent installation of additional equipment. Labeling option directly on the device. Suitable for subsequent installation of additional equipment.Rated current25 AType of differential protectionASensitivity30 mANumber2 PImpact current resistance (pulse fault currents 8/20μs)0,25Number of modules2Frequency50 HzAssembly typeDIN railConnection typeQuickConnectConnection cross section with flexible conductor16mm2Connection cross section for rigid conductor25mm2Torque2.8 NmType of protectionIP20Insulation voltage500 VImpact strength4 kVAdditional equipment possible1Operating temperature-25 to 40 °CMachine life mechanical switching games4000Device life, electrical switching games2000Total loss power at rated current3.4 WDegree of contamination according to IEC 60664 / IEC 60947-22Height above N.N.2000 mRated current at 30° C25 AStorage temperature-55 to 70 °CHeight installed product83 mmWide installed product35 mmDeep Installed Product70 mm
€75.48
Hager CDS425D Fehlerstromschutzschalter 4 polig 6kA 25A 30mA Typ A QuickConnect
Hager CDS425D fault current switch 4 polig 6kA 25A 30mA Type A QuickConnect
3-7 working days
EN 61008-1, DIN EN 61008-2-1 and VDE 0664 Part 10 + 11. QuickConnect terminal according to DIN EN 60898-1, VDE 0641-11 at access up to 63 A, IP2x touch protection according to DIN VDE 0106 part 100, blue test button and fault current display. Simple individual removal from the phase rail composite. With VDE characters. Suitable for subsequent installation of additional equipment. Labeling option directly on the device. Suitable for subsequent installation of additional equipment. Nominal current: 25 A Type of differential protection: A Sensitivity: 30 mA Number of poles: 4 P Impact current strength (impulsive fault currents 8/20μs): 0.25 kA Number of modules: 4 Frequency: 50 Hz Rated current25 AType of differential protectionASensitivity30 mANumber4 PImpact current resistance (pulse fault currents 8/20μs)0,25Number of modules4Frequency50 HzAssembly typeDIN railConnection typeQuickConnectConnection cross section with flexible conductor16mm2Connection cross section for rigid conductor25mm2Torque2.8 NmType of protectionIP20Insulation voltage500 VImpact strength4 kVAdditional equipment possible1Operating temperature-25 to 40 °CMachine life mechanical switching games4000Device life, electrical switching games2000Total loss power at rated current4.5 WDegree of contamination according to IEC 60664 / IEC 60947-22Height above N.N.2000 mRated current at 30° C25 AStorage temperature-55 to 70 °CHeight installed product83 mmWide installed product70 mmDeep Installed Product70 mm
€75.48
Hager CDA240D Fehlerstromschutzschalter 2 polig 6kA 40A 30mA Typ A
Hager CDA240D fault current switch 2 polig 6kA 40A 30mA Type A
Out-of-Stock
Rated current40 AType of differential protectionASensitivity30 mANumber2 PImpact current resistance (pulse fault currents 8/20μs)0,25Number of modules2Frequency50 HzAssembly typeDIN railConnection typeScrew technologyConnection cross section with flexible conductor16mm2Connection cross section for rigid conductor25mm2Torque2.8 NmType of protectionIP20Insulation voltage500 VImpact strength4 kVAdditional equipment possible1Operating temperature-25 to 40 °CMachine life mechanical switching games4000Device life, electrical switching games2000Total loss power at rated current9.2 WDegree of contamination according to IEC 60664 / IEC 60947-22Height above N.N.2000 mRated current at 20° C40 ARated current at 30° C40 ARated current at 35° C40 ARated current at 40° C40 ARated current at 45° C38 ARated current at 50°C37 ARated current at 55° C34 ARated current at 60°C30 ARated current at 65°C26 ARated current at 70°C21 AStorage temperature-55 to 70 °CHeight installed product83 mmWide installed product35 mmDeep Installed Product70 mm
Hager CDA425D Fehlerstromschutzschalter 4 polig 6kA 25A 30mA Typ A
Hager CDA425D fault current circuit breaker 4 polig 6kA 25A 30mA Type A
Out-of-Stock
fault current protection switch 4 polig 6kA 25A 30mA type A. fault current protection switch (FI) according to EN 61008-1, DIN EN 61008-2-1, VDE 0664 part 10 + 11, touch protection IP2x according to DIN VDE 0106 part 100. Suitable for subsequent mounting of additional devices (mount without tool). Connection terminals with wire insertion protection, Bi-Connect terminals at the bottom, external blue test button. All products with VDE characters. Labeling option directly on the device.Rated current25 AType of differential protectionASensitivity30 mANumber4 PImpact current resistance (pulse fault currents 8/20μs)0,25Number of modules4Frequency50 HzAssembly typeDIN railConnection typeScrew technologyConnection cross section with flexible conductor16mm2Connection cross section for rigid conductor25mm2Torque2.8 NmType of protectionIP20Insulation voltage500 VImpact strength4 kVAdditional equipment possible1Operating temperature-25 to 40 °CMachine life mechanical switching games4000Device life, electrical switching games2000Total loss power at rated current4.5 WDegree of contamination according to IEC 60664 / IEC 60947-22Height above N.N.2000 mRated current at 20° C25 ARated current at 30° C25 ARated current at 35° C25 ARated current at 40° C25 ARated current at 45° C25 ARated current at 50°C25 ARated current at 55° C25 ARated current at 60°C25 ARated current at 65°C22 ARated current at 70°C18 AStorage temperature-55 to 70 °CHeight installed product83 mmWide installed product70 mmDeep Installed Product70 mm
Hager CDA225D Fehlerstromschutzschalter 2 polig 6kA 25A 30mA Typ A
Hager CDA225D fault current switch 2 polig 6kA 25A 30mA Type A
3-8 working days
Residual current circuit breaker 2-pole 6kA 25A 30mA type A. Residual current circuit breaker (FI) according to EN 61008-1, DIN EN 61008-2-1, VDE 0664 part 10 + 11, protection against accidental contact IP2x according to DIN VDE 0106 part 100 .Suitable for retrofitting additional equipment (mounting without tools). Wire push-in protection terminals, bottom bi-connect terminals, external blue test button. All products with VDE mark. Labeling option directly on the device.



Rated current
25A


Type of differential protection
A


Sensitivity
30mA


Number of Poles
2P


Surge current resistance (pulse fault currents 8/20µs)
0.25kA


Number of modules
2


Frequency
50Hz


Mounting type
DIN rail


Type of connection
screw technology


Connection cross section with flexible conductor
16mm²


Connection cross section with rigid conductor
25mm²


torque
2.8Nm


degree of protection
IP20


Insulation voltage
500V


Surge withstand voltage
4kV


Additional equipment possible
1


Operating temperature
-25 to 40 °C


Device lifetime mechanical switching cycles
4000


Device service life, electrical switching cycles
2000


Total power loss under rated current
3.4W


Degree of contamination according to IEC 60664 / IEC 60947-2
2


Height above sea level
2000m


Rated current at 20° C
25A


Rated current at 30° C
25A


Rated current at 35° C
25A


Rated current at 40° C
25A


Rated current at 45° C
25A


Rated current at 50°C
25A


Rated current at 55° C
25A


Rated current at 60°C
25A


Rated current at 65°C
25A


Rated current at 70°C
21A


Storage temperature
-55 to 70 °C


Height installed product
83mm


Wide installed product
35mm


Deep Installed Product
70mm


€68.04
Hager CDA440D Fehlerstromschutzschalter 4 polig 6kA 40A 30mA Typ A
Hager CDA440D fault current circuit breaker 4 polig 6kA 40A 30mA Type A
2-5 days
Rated current: 40 ANumber of poles: 4 PSensitivity: 30 mAType of differential protection: AImpact strength: 4 kVNumber of modules: 4AC voltage: 230/400 VInsulation voltage: 500 VFrequency: 50 HzTorque: 2,8NmConnection type: screw technologyTotal loss power at rated current: 6.5 WDevice life, electrical switching games: 2000Machine life mechanical switching games: 4000Connection cross-section with flexible conductor: 16mm2Connection cross section for rigid conductor: 25mm2Operating temperature: -25 to 40 °CStorage temperature: -55 to 70 °CHeight installed product: 83 mmWide installed product: 70 mmDeep installed product: 70 mm
€63.76